Images are representations only.

Series DCT1000DC Dust Collector Timer Controller

Brand: Dwyer Instruments, LLC

Free Shipping on Orders Over $365.72 USD

Simplify your on-demand cleaning requirements with the Series DCT1000DC Dust Collector Timer Controller.

Relying on one timer board for on demand and continuous cleaning applications, the DCT1000DC eliminates external devices such as pressure switches, relays and timers.

The DCT1000DC accepts 10-30 VDC power. The units modular design allows for use as a continuous cleaning control or on demand cleaning control using the optional DCP plug-in pressure module.

A 4-20 mA process output is integral to the DCP pressure module, eliminating the need to purchase an expensive process transmitter. A solenoid fault light on the DCT1000DC notifies the operator when a solenoid valve fails to activate properly.

The DCT1000DC is the same size for 6, 10 and 22 channels. One board size allows the standardization on one enclosure.
Features
  • 10 to 30 Vdc power requirement for low voltage applications
  • Standard mounting holes to other dust collector controllers for use in existing installations
  • Able to automatically detect any channel expander connected
show more
Simplify your on-demand cleaning requirements with the Series DCT1000DC Dust Collector Timer Controller.

Relying on one timer board for on demand and continuous cleaning applications, the DCT1000DC eliminates external devices such as pressure switches, relays and timers.

The DCT1000DC accepts 10-30 VDC power. The units modular design allows for use as a continuous cleaning control or on demand cleaning control using the optional DCP plug-in pressure module.

A 4-20 mA process output is integral to the DCP pressure module, eliminating the need to purchase an expensive process transmitter. A solenoid fault light on the DCT1000DC notifies the operator when a solenoid valve fails to activate properly.

The DCT1000DC is the same size for 6, 10 and 22 channels. One board size allows the standardization on one enclosure.
Features
  • 10 to 30 Vdc power requirement for low voltage applications
  • Standard mounting holes to other dust collector controllers for use in existing installations
  • Able to automatically detect any channel expander connected

Specifications

Accuracy

  • ± 1 % of the Value
  • ± 1.5 % of Full Scale at 22.8° C (73° F)
  • ± 10 millisecond (On Time Accuracy)
  • ± 50 millisecond - whichever is greater (off Time Accuracy)

Approvals & Certifications

  • CE

Differential Pressure

  • psi: 10 (kPa: 68.95, bar: 0.6895)

Electrical Rating

  • 1.5 A Inductive Load at 30 Vac or 40 Vdc - Alarm Contacts
  • 3 A at Resistive Load at 30 Vac or 40 Vdc - Alarm Contacts

Output

  • 10-Channels - Output Channels
  • 22-Channels - Output Channels
  • 4-20 mA
  • 6-Channels - Output Channels

Power Requirement

  • 10-30 Vdc
  • 3 A at 250 Vac - (Fuse)

Pressure Range

  • Inches WC: 0 to 200

Response Time

  • 1 to 255 seconds - 1 second steps (off time)

Storage Temperature

  • -40° to 80° C (-40° to 176° F)

Supply Pressure

  • psi: 10 (kPa: 68.95, bar: 0.6895)

Temperature Range

  • -40° to 60° C (-40° to 140° F)

Tube Connection

  • 1/8” (3.18 mm) - I.D. Tubing Two Barbed Connections
  • 3/16” (4.76 mm) - I.D. Tubing Two Barbed Connections

Turn-On Time

  • 10 to 600 milliseconds - 10 millisecond steps (On-Time)

Applications

  • Dust Collection
  • Pneumatic Conveying